Recommended size
-
Corrected ampacity
-
Voltage drop
-
| Size | Corrected ampacity | Ampacity ok | VD percent | VD ok |
|---|
Base ampacity from NEC Table 310.16, DC resistance from Chapter 9 Table 8 (uncoated), two-way voltage drop. PV source/output circuits apply Isc x 1.25 (690.8(A)(1), irradiance factor) x 1.25 (690.8(B)(1), continuous duty) = 1.5625x. Ambient correction uses sqrt((Tc-Ta)/(Tc-30)) so the rooftop adder stacks precisely. Educational estimate only, not a substitute for a licensed engineer's stamped design.