PVeducation.com

All About Solar Electric Systems and Components

  • Welcome
  • About
  • General Information
    • Working Safely with Photovoltaic Systems
    • Climate-101
    • Leasing Solar Systems
  • Solar Module Quality
    • Poor Quality Solar Module
    • Poor Quality Control – Solar Cell Color Differences
    • Snail Trails
  • Solar Concepts
    • Solar Cells, Modules, and Arrays
    • Series and Parallel Wiring
    • Sun Path
    • Solar Azimuth
    • Roof Pitch and Roof Angle (Degrees)
    • Electrical Fundamentals
    • Weight of Typical Pitched Roof Solar System
    • Solar PV Module Efficiency
    • Fixed or Tracking Array
    • Shadow Calculations for Row Spacing
    • Battery State of Charge vs Open Circuit Battery Voltage
    • Solar System Output
    • sREC – Solar Renewable Energy Credits
    • Roof Zones
    • Common Electrical Services
  • Solar System Types
    • Grid Tied Residential and Small Commercial Solar System with String Inverter
    • Grid Tied Residential and Small Commercial Solar System with Micro Inverters
    • Solar System with Direct Load
    • Grid Tied Large Commercial Solar System
    • Off Grid Solar System with DC Loads
    • Off Grid Solar System with DC and AC Loads
    • Grid Tied Battery Backup Solar System
  • Designing an Off Grid Solar Electric System
    • Designing an Off Grid Solar Electric System, Step 1, Planning Considerations
    • Designing an Off Grid Solar Electric System, Step 2, Determine the Total Load
    • Designing an Off Grid Solar Electric System, Step 3a, Determine the Amount of Solar Needed Using an MPPT Controller
    • Designing an Off Grid Solar Electric System, Step 4, Sizing the Battery Bank
    • Stand-Alone Photovoltaic Systems Book
  • System Design Equations
    • Calculate Array Voltage
  • Solar Installation Failures and What Not To Do
    • Squirrel Damage
    • Using the Wrong Disconnect
    • Poor Fused Combiner Design
    • Wrong Conduit
    • Improper Row Spacing
    • Badly Placed Conduit and Bad Roof Penetration
    • Inverter Commissioning
    • Water Filled Enclosures
  • Design Parameters
    • Conductor Ampacity of AL
    • Conductor Ampacity of CU
    • Temp Adjustment Conduit on Roof
    • Conduit Fill Table
    • Adjustment Factors Qty of Conductors
    • Solar Radiation by State
    • US Irradiance Maps
    • Wind Speed, Snow Load, Seismic Ratings, Temperature
You are here: Home / Design / Conductor Ampacity of AL

Conductor Ampacity of AL

As a solar system is designed you need to select the correct size conductor. The following tables will help in that selection. This information is based on the following:

  • National Electric Code (NEC) Table 310.16
  • Conductors rated 0 to 2000 V
  • Not more than 3 current carrying conductors in raceway, cable or direct buried
  • Ambient Temp 30C (86F)

Allowable Ampacity of Aluminum Conductors

Size AWG or kcmilConductor Temp
60C (140F)
Conductor Temp
75C (167F)
Conductor Temp
90C (194F)
12*202025
10*253035
8304045
6405060
4556575
3657585
27590100
185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250170205230
300190230255
350210250280
400225270305
500260310350

*12 AWG Maximum overcurrent = 15 amps
*10 AWG Maximum overcurrent = 25 amps

Correction Factors for Different Ambient Temperatures

For ambient temperatures other than 30C (86F) the following are multipliers used to adjust the above ampacity.  As the temperature of a conductor increases the amount of current the conductor can safety carry is reduced.

Ambient
Temperature (C)
Conductor Temp
60C (140F)
Conductor Temp
75C (167F)
Conductor Temp
90C (194F)
Ambient
Temperature (F)
21-251.081.051.0470-77
26-3011178-86
31-350.910.940.9687-95
36-400.820.880.9196-104
41-450.710.820.87105-113
46-500.580.750.82114-122
51-550.410.670.76123-131
56-6000.580.71132-140
61-7000.330.58141-158
71-80000.41159-179