Conduit Fill Table

Conduit Fill Table

As you design a solar system you will often need to know how many conductors can fit into a conduit. This is a quick reference to help you.

  • Based on NEC2014 Table C
  • Wire Type is THHN, THWN, THWN-2
Conduit Size Conduit Type 14AWG 12AWG 10AWG 8AWG 6AWG 4AWG 3AWG 2AWG 1AWG 1/0AWG 2/0AWG 3/0AWG 4/0AWG 250kcmil 300kcmil 350kcmil 400kcmil 500kcmil
1/2” EMT 12 9 5 3 2 1 1 1 1 1 0 0 0 0 0 0 0 0
  PVC 11 8 5 3 1 1 1 1 1 1 0 0 0 0 0 0 0 0
3/4” EMT 22 16 10 6 4 2 1 1 1 1 1 1 1 0 0 0 0 0
  PVC 21 15 9 5 4 2 1 1 1 1 1 1 1 0 0 0 0 0
1” EMT 35 26 16 9 7 4 3 3 1 1 1 1 1 1 1 1 0 0
  PVC 34 25 15 9 6 4 3 3 1 1 1 1 1 1 1 0 0 0
1-1/4” EMT 61 45 28 16 12 7 6 5 4 3 2 1 1 1 1 1 1 1
  PVC 60 43 27 16 11 7 6 5 3 3 2 1 1 1 1 1 1 1
1-1/2” EMT 84 61 38 22 16 10 8 7 5 4 3 3 2 1 1 1 1 1
  PVC 82 59 37 21 15 9 8 7 5 4 3 3 2 1 1 1 1 1
2” EMT 138 101 63 36 26 16 13 11 8 7 6 5 4 3 3 2 1 1
  PVC 135 99 62 36 26 16 13 11 8 7 6 5 4 3 3 2 1 1
2-1/2” EMT 241 176 111 64 46 28 24 20 15 12 10 8 7 6 5 4 4 3
  PVC 193 141 8 51 37 22 19 16 12 10 8 7 6 4 4 3 3 2
3” EMT 364 266 167 96 69 43 36 30 22 19 16 13 11 9 7 6 6 5
  PVC 299 218 137 79 57 35 30 25 18 15 13 11 9 7 6 5 5 4
3-1/2” EMT 476 347 219 126 91 56 47 40 29 25 20 17 14 11 10 9 8 6
  PVC 401 293 184 106 77 47 40 33 25 21 17 14 12 10 8 7 6 5
4” EMT 608 443 279 161 116 71 60 51 37 32 26 22 18 15 13 11 10 8
  PVC 517 377 238 137 99 61 51 43 32 27 22 18 15 12 11 9 8 7